The AL105NX is the industry standard for combined audible and visual signaling. The high output 113dB(A) alarm horn sounder is combined with a 5 Joule, 200cd Xenon strobe beacon. CPR complaint, EN54-3 & EN54-23 tested and UL/cUL approved for private mode fire use. Featuring 64 alarm tone frequencies and 4 remotely activated stages/channels.
Globally approved for fire, marine and general applications the low current consumption and high SPL in a robust fire retardant enclosure ensure the AL105NX is suitable for all signalling applications including fire, security and process control. The alarm horn sounder & Xenon strobe beacon may be connected from a single or separate supplies for simultaneous or independent operation.
Automatic synchronisation
Continuously rated
Dual M20x1.5mm threaded cable entries - adaptors available
Duplicate pluggable cable terminations - Class A
Ingress protection IP66 Type 4/4X/13/3R
64 alarm tone frequencies and 4 remotely activated alarm stages
Available with custom tone configurations and frequencies
Diode polarized for use in supervised circuits
Alarm Horn:
Maximum output: 113dB(A) @ 1 m ±3dB [104dB(A) @ 10ft/3m ±3dB]
Nominal output: 106dB(A) @ 1m ±3dB [97dB(A) @ 10ft/3m ±3dB]
No. of tones: 64 (UKOOA / PFEER compliant)
No. of stages: 4
Volume control: -12dB(A) tone dependent
Effective range: 58m/190ft @ 1KHz
In rush: 636mA within 4.0ms @ 24Vdc
Stage switching: Negative (common positive)
Xenon Strobe:
Energy: 5 Joules(5Ws)
Flash rate: 1Hz (60 fpm)
DC units: 1.5Hz (90 fpm) & Double strike
Peak Candela: 500,000 cd – calculated from energy (J)
Effective cd: 250 cd – calculated from energy (J)
Peak Candela: 86,935 cd* – measured ref. to I.E.S.
Effective cd: 200 cd* – measured ref. to I.E.S.
Tube life: Emissions may reduce to 70% after 8 million flashes
General:
Ingress protection: IP66 Type 4/4X/13/3R
Enclosure: High impact UL94 V0 & 5VA FR ABS/PC
Lens colour filter: Field replaceable UV stable PC
Terminals: 0.5 – 2.5mm² (20-14 AWG)
Line monitoring: Diode polarized for use in supervised circuits
Operating: -40 to +66°C [-40° to +151°F]
Storage: -40 to +70°C [-40° to +158°F]
Relative humidity: 95% at 20°C [68°F]
Vibration test: 35Hz for a duration 4Hr (UL464/UL1638)
Jarring test: 3ft/lb Energy (UL464/UL1638)
Impact test: 3x 5lb (UL464/UL1638)
MTBF DC: 114.79 years / 1,005,530 hours – MIL 217
MTBF AC: 86.29 years / 755,857 hours – MIL 217
Weight DC: 0.95kg / 2.10Ibs
Weight AC: 1.20kg / 2.64Ibs